SOLICITATION NOTICE

41 -- Belt Driven Centrifugal fans

Notice Date
8/4/2010
 
Notice Type
Combined Synopsis/Solicitation
 
NAICS
333412 — Industrial and Commercial Fan and Blower Manufacturing
 
Contracting Office
Department of Health and Human Services, National Institutes of Health, National Cancer Institute, Bldg 427, Room 12, Frederick, Maryland, 21702
 
ZIP Code
21702
 
Solicitation Number
A56891
 
Archive Date
8/21/2010
 
Point of Contact
Chuck Gartner, Fax: 301-846-5311
 
E-Mail Address
gartnerch@mail.nih.gov
(gartnerch@mail.nih.gov)
 
Small Business Set-Aside
N/A
 
Description
TWIN CITY FAN MODEL TSL-222 TUBULAR INLINE BELT DRIVEN CENTRIFUGAL FAN, CLASS II, ARRANGEMENT 9 CFM: 8000 @ 3 IN.WG SP @ 1760 RPM MOTOR: 7-1/2 HP TEFC PREMIUM EFFICIENCY INVERTER DUTY 1800RPM, 480V/3PH/60HZ ACCESSORIES: BOLTED ACCESS DOOR, FLANGED INLET/OUTLET, COMPANION INLET/OUT FLANGES, BELT GUARD, SPRING HANGERS/VIBRATION ISOLATORS, CEILING MOUNTING BRACKETS, EXTENDED LUBRICATION LINES, UNFUSED DISCONNECT SWITCH 1 EA. TWIN CITY FAN MODEL JRW-807F BELT DRIVEN CENTRIFUGAL FAN, SWSI, CLASS SD, ARRANGEMENT 9, CCW, BAU OPPOSITE DISCHARGE CFM: 1100 @ 3 IN.WG. SP @ 2643 RPM MOTOR: 3 HP TEFC PREMIUM EFFICIENCY 1800 RPM, 480V, 3PH/60HZ ACCESSORIES: ACCESS DOOR, 3/4" DRAIN CONNECTION, BELT/SHAFT/BEARING GUARDS, TYPE B SPARK RESISTANT DESIGN, RIS VIBRATION ISOLATORS, UNFUSED DISCONNECT SWITCH (NEMA 3R), GRAVITY OPERATED DISCHARGE SHUTTER TYPE DAMPER 1EA. 1) The catalog numbers listed are from Twin City Fan. 2) Offerors are requested to quote on the item as specified or an equivalent 3) "Equivalent" offers shall provide complete specifications and/or descriptive literature for any alternates offered, stating catalog number, manufacturer, packaging. Offerors are requested to indicate any differences from the specifications listed. Failure to provide complete information may cause offer to be non-responsive 4) Warranty period shall be ______ months, including parts, labor and travel 5) All offers must be F.O.B. destination 6) Any shipping charges must be identified and listed on the response for evaluation. 7) Freight over $250.00. If any freight charge exceed $250.00 a separate invoice must be sent. A copy of the actual freight bill must be included with the invoice. 8) Partial offers will not be accepted. 9) SAIC-Frederick, Inc. is eligible for Federal Supply Schedule pricing. 10) Offeror agrees to make delivery of the quoted items in _____ days after receipt of order
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/HHS/NIH/FCRF/A56891/listing.html)
 
Place of Performance
Address: SAIC-Frederick, 7116 Geoffrey Way, Frederick, MD 21704, United States
Zip Code: 21704
 
Record
SN02229362-W 20100806/100804235637-d3c7f82eef7cfda68dfcb2ab96567848 (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.