Loren Data's SAM Daily™

fbodaily.com
Home Today's SAM Search Archives Numbered Notes CBD Archives Subscribe
FBO DAILY - FEDBIZOPPS ISSUE OF APRIL 14, 2016 FBO #5256
MODIFICATION

48 -- 14" Swing Check Valves, 5 Each

Notice Date
4/12/2016
 
Notice Type
Modification/Amendment
 
NAICS
332911 — Industrial Valve Manufacturing
 
Contracting Office
Department of the Army, U.S. Army Corps of Engineers, USACE District, Little Rock, Attn: CESWL-CT, PO Box 867, Little Rock, Arkansas, 72203-0867, United States
 
ZIP Code
72203-0867
 
Solicitation Number
W9127S-16-T-0025
 
Archive Date
4/29/2016
 
Point of Contact
Robert E.Buchanan, Phone: 501-340-1257
 
E-Mail Address
robert.e.buchanan@usace.army.mil
(robert.e.buchanan@usace.army.mil)
 
Small Business Set-Aside
Woman Owned Small Business
 
Description
Question #6: Powell states that as a standard, the requested MSS SP-71 14 inch valves do undergo a shell test at the listed 265 psi test pressure, however Powell's standard is only a one (1) minute minimum pressure test duration for a valve this size. Powell MSS SP-71 Swing Check valve design is Bolted Bonnet, Flanged ends design, and as such, Powell does not do a separate mechanical joint tightness test to prove bonnet/mechanical joint integrity, performed to a pressure equal to the rated working pressure. Powell states that a shell test performed at a minimum 1.5 times the working pressure with test results that pass, doing the exact same test at a lower pressure would not accomplish a different result for the joint tightness of the bonnet/mechanical joint. Powell Check Closure test acceptance standards for the Powell MSS SP-71 are listed as being 560 ml/hr. Are the Powell pressure and leakage test standards for the requested 14 inch MSS SP71 valves acceptable? Answer: Testing requirements have not changed, Bull Shoals power plant still remains steadfast - a hydrostatic test and mechanical joint tightness test ARE required for this solicitation.
 
Web Link
FBO.gov Permalink
(https://www.fbo.gov/spg/USA/COE/DACA03/W9127S-16-T-0025/listing.html)
 
Place of Performance
Address: Bull Shoals Power Plant, 2737 Powerhouse Road, Lakeview, Arkansas, 72642, United States
Zip Code: 72642
 
Record
SN04081951-W 20160414/160413001159-ac60f1d7d60f51f4546acd500b28e97c (fbodaily.com)
 
Source
FedBizOpps Link to This Notice
(may not be valid after Archive Date)

FSG Index  |  This Issue's Index  |  Today's FBO Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2024, Loren Data Corp.