SOLICITATION NOTICE
61 -- 100 kW Diesel Generator
- Notice Date
- 6/12/2020 6:26:40 AM
- Notice Type
- Combined Synopsis/Solicitation
- NAICS
- 335312
— Motor and Generator Manufacturing
- Contracting Office
- W07V ENDIST ST PAUL SAINT PAUL MN 55101-1678 USA
- ZIP Code
- 55101-1678
- Solicitation Number
- W912ES20T0113
- Response Due
- 6/25/2020 9:00:00 AM
- Archive Date
- 07/10/2020
- Point of Contact
- John P Riederer, Phone: 6512905614
- E-Mail Address
-
john.p.riederer@usace.army.mil
(john.p.riederer@usace.army.mil)
- Small Business Set-Aside
- SBA Total Small Business Set-Aside (FAR 19.5)
- Description
- The U.S. Army Corps of Engineers - St. Paul District requires a contractor to supply one (1) U.S. EPA Tier 4/IMO certified Diesel generator set, producing prime 100 KW / 480 volt 3 phase / 60 Hz. The generator will be installed by Government personnel as the primary power source for the Dredging Barge Wade.� The contract resulting from this solicitation will be for supplying the generator. No installation services are required. The generator design shall be a permanent magnet excitation type. (PMG) The installed voltage regulator will have 3 phase sensing. The voltage regulator shall be adjustable to compensate for engine speed droop and line loss. The generator shall be of a close coupled single bearing design. The generator shall incorporate H class insulation. To prevent condensation from forming in the generator it will have anti-condensation heaters installed inside the generator. The diesel engine will be electrically governed. The electronic system shall display diagnostic and fault codes, to include an emergency shutdown devise. The engine at a minimum shall have shutdowns for low oil pressure, high jacket water temperature and overspeed. The engine shall incorporate an engine coolant block heater. The internal fuel tank shall be of a double wall design with no less than 150 gallons of capacity. The generator set will be equipped with an outdoor enclosure with a level of sound output to be less than 75 dBA. The dimensions of the generator cannot exceed 50"" width and 127"" in length. OFFEROR SHALL BE REGISTERED IN SAM (System for Award Management)� https://www.sam.gov to include the FAR and DFARS Reps and Certs sections with the NAICS code applicable to the solicitation. Quotes received after the solicitation close time and date may not be considered for award. Item pricing quoted shall include all fees, tariffs, taxes and delivery FOB Destination (Fountain City, WI). Please DO NOT quote delivery fees separately. QUOTES MUST INCLUDE a cut-sheet, providing the manufacturer, model, specifications, and data sufficient to demonstrate that the product offered fully meets SOW specifications. Delivery shall be within one month of contract award.
- Web Link
-
SAM.gov Permalink
(https://beta.sam.gov/opp/6f94bfa7ef2942ce91c95185cda99d36/view)
- Place of Performance
- Address: Fountain City, WI 54629, USA
- Zip Code: 54629
- Country: USA
- Zip Code: 54629
- Record
- SN05689030-F 20200614/200612230152 (samdaily.us)
- Source
-
SAM.gov Link to This Notice
(may not be valid after Archive Date)
| FSG Index | This Issue's Index | Today's SAM Daily Index Page |