Loren Data's SAM Daily™

fbodaily.com
SAMDAILY.US - ISSUE OF SEPTEMBER 23, 2026 SAM #9067
SOLICITATION NOTICE

46 -- Engineering Request - SPS REVERSE OSMOSIS | 538-26-3-6064-0049 (VA-26-00079545) - VAMC Chillicothe

Notice Date
9/21/2026 9:45:35 AM
 
Notice Type
Combined Synopsis/Solicitation
 
NAICS
221310 — Water Supply and Irrigation Systems
 
Contracting Office
250-NETWORK CONTRACT OFFICE 10 (36C250) DAYTON OH 45428 USA
 
ZIP Code
45428
 
Solicitation Number
36C25026Q1034
 
Response Due
9/22/2026 12:00:00 PM
 
Archive Date
10/22/2026
 
Point of Contact
Christopher A. Callihan, Contracting Officer, Phone: 216-707-7736, Fax: N/A
 
E-Mail Address
christopher.callihan@va.gov
(christopher.callihan@va.gov)
 
Small Business Set-Aside
SBA Small Business Set Aside - Total
 
Description
The purpose of this amendment is to post questions received and provide the facilities responses. The response date and time remain unchanged. Are the 0.2 Micron Filter Cartridges the ones that are for the tank vent filter we would be providing? Or is this for an existing endotoxin filter housing the facility has? 0.2 Micron Filter Cartridges are for bacterial removal from water and to be compatible with housing provided under CLIN 0003. Tank vent cartridges are maintained separately and not within scope. What flow rates do the 60-gallon and 160-gallon storage tank loop return need to handle? Specifically, when sizing the loop return flow meter we need to ensure it can handle the pump demand. I would assume 20 GPM and 40 GPM based on the UV assembly? Return is being constrained via 3gpm flow control device. Pumps are pressure sensing variable flow rate. Both flow control and pumps are not within scope of the solicitation. UV sized for peak demand. Are there existing pumps within the facility that they are keeping? I do not see a distribution pump mentioned in this bid. Pumps are not within scope. Do you have a list of existing equipment that is being kept for both systems? No What are the distribution loop sizes, loop material and loop length are they existing or is this a new loop? Modifying existing loop. Mixed materials, CPVC and Polypropylene. Loop is approximately 240 LF with mixed sizes of 1 and 1-1/2
 
Web Link
SAM.gov Permalink
(https://sam.gov/workspace/contract/opp/c3b3cdffd5a5455285dda9229cf65ed1/view)
 
Place of Performance
Address: Department of Veterans Affairs Chillicothe VAMC 17273 State Route 104, Chillicothe, OH 45601, USA
Zip Code: 45601
Country: USA
 
Record
SN07979186-F 20260923/260921230052 (samdaily.us)
 
Source
SAM.gov Link to This Notice
(may not be valid after Archive Date)

| FSG Index  |  This Issue's Index  |  Today's SAM Daily Index Page |
ECGrid: EDI VAN Interconnect ECGridOS: EDI Web Services Interconnect API Government Data Publications CBDDisk Subscribers
 Privacy Policy  Jenny in Wanderland!  © 1994-2026, Loren Data Corp.