COMMERCE BUSINESS DAILY ISSUE OF JULY 20,1995 PSA#1392National Institute of Standards and Technology, Acquisition and
Assistance Division, Building 301, Room Bll7, Gaithersburg, MD 20899 56 -- MANUFACTURED CEILING SYSTEM POC POC: Paul Cataldo (301)
975-6332/C.O.: Pauline Mallgrave (301) 975-6330 The National Institute
of Standards and Technology, Gaithersburg, MD is seeking sources for
its proposed 42,236 gross square meter Advanced Technology Laboratory
who can provide a manufactured ceiling system consisting of steel faced
panels constructed of a minimum of two each 1 mm minimum electrozinc
steel panels enclosing extruded polystyrene, rockwool, or other
suitable inert insulation material for a total thickness of
approximately 85mm enclosed at the edges by a cold formed steel frame--
Panels shall be part of a system which includes integral connectors for
interlocking adjacent panels at their joints, adjustable suspension
devices which provide a support means to the panels as well as provide
a means for their attachment to the structure, and the necessary trim
pieces providing an aesthetically pleasing and flat, flush and
homogeneous ceiling surface conducive to cleaning and the maintaining
of a clean laboratory environment- -Additionally, the panel system
shall have the capability to support loads resulting from maintenance
and repair personnel walking on the panels on their upper
surfaces--Panel system shall be capable of supporting a concentrated
load of 125 daN at any 300mm x 300mm spot on the face of a panel, and
must be capable of supporting a maximum uniformly distributed load of
approximately 1500 N/m2--Panel sizes are 900mm and 1200mm in width and
1800mm in length and shall be manufactured to metric
dimensions--Panels shall be engineered with a minimum safety factor of
3 based on ultimate strength under static loading conditions and shall
not deflect more than 1/720 of the span in either the vertical or
horizontal plane when maximum loading conditions are applied--The
Panels shall be non- shedding and non-outgassing and shall be
non-progressive in their installation and removal--Panels shall have an
STC rating of approximately 45, and shall be coated with a minimum 45
micron epoxy coating. System shall include all integrated fittings,
penetrations, and all required gaskets, trim pieces, sealants and
accessories necessary for a complete and functioning
installation--Interested sources should submit all information
necessary for the Government to fully evaluate the proposed product and
should include but not necessarily be limited to any and all catalog
cut sheets, product brochures, drawings, calculations, and technical
data which is necessary to demonstrate the proposed product fully meets
the performance and functional criteria stated above--Contact Paul
Cataldo, National Institute of Standards and Technology, Acquisition
and Assistance Division, Building 301, Room B117, Gaithersburg, MD
20899-0001 within 30 days of this publication.(0199) Loren Data Corp. http://www.ld.com (SYN# 0499 19950719\56-0002.SOL)