COMMERCE BUSINESS DAILY ISSUE OF NOVEMBER 9,1995 PSA#1470Naval Undersea Warfare Center Division, Newport Commercial Acquisition
Department, Code 09, Building 11, Newport, RI 02841-5407 34 -- AUTONOMOUS SOLAR POWER SYSTEM SOL N66604-96-R-A382 DUE 120195
POC Contact Mary Jo Nemec, Contracting Officer at (401) 841-2442 X 296
FAX: (401) 841-4820 The Naval Undersea Warfare Center Division
Newport,RI (NUWCDIVNPT) is soliciting quotations by this synopsis for
the acquisition of two (2) SOLAR ELECTRIC POWER SYSTEMS. An autonomous
solar power system is being purchased which shall provide power
continuously and independently for the Sonobuoy Tracking System (STS)
in use at the Atlantic Undersea Test and Evaluation Center (AUTEC). 2.2
REQUIREMENTS The solar power system at a minimum shall include the
following 1. Solar Panels 2. Battery Bank 3. Battery Charge Controller
4. DC to AC Power Inverter 5.Solar Panel Mounting Structure 6. Battery
Bank Storage System 7. Solar Panel Wiring 8AC Output Terminal 9.
Battery Bank Interconnect Wiring 10. 2.3 SOLAR PANELS: The solar panels
shall provide the necessary current capability for charging the battery
bank. The output voltage shall be compatible with that required by the
charge controller unit and the battery bank. 2.4 OUTPUT POWER The
output voltage shall be 110 V ac,+/- 4%. The continuous Output Power
capability of the system shall support a 5A load. The system shall also
be capable of supporting a temporary 15A load, +/- 4A, for a duration
of 8 hours. 2.5 BATTERY BANK The size of the battery bank shall support
five days system operation without solar charging. The batteries shall
have a minimum 135 amp-hour rating at a 20 hour rate. The battery bank
shall have a minimum of two parallel sets of batteries connected in
series. There shall be at least three independent connections between
the parallel sets. The size of the individual battery units shall be
20.75'' x 11'' x 10'' +/- 6''. 2.6 CHARGE CONTROLLER The charge
controller shall regulate the solar panel output current and/or voltage
for charging the battery bank. The controller shall have a low voltage
disconnect capability to protect the battery bank should the output
voltage of the solar panels fall below the battery bank voltage. 2.7
DC-AC INVERTER The inverter shall be a true sine wave inverter. The
inverter shall provide surge protection and continuous output power to
the load. The surge protection shall beable to start a load of six
times the nominal load of section 2.4. The inverter shall provide a
minimum of 8 A load current capacity at 110 V for continuous power. A
minimum of two ac outlets shall be provided. 2.8 MISCELLANEOUS
EQUIPMENT The following equipment shall be provided for each system.
SOLAR PANELS MOUNTING STRUCTURE: The solar panels mounting structures
shall at a minimum hold 4 solar panels per structure. The mounting
structures shall be ground mount structures capable of being mounted on
the roof. The structures shall weigh less than 100 lbs. Hardware shall
be provided for mounting the solar panels. BATTERY BANK STORAGE
SYSTEM: A battery enclosure shall be provided to enclosed the battery
bank. The enclosure shall be a ventilated enclosure to prevent gas
build up. The enclosures shall at a minimum have the following
characteristics: 5/16'' minimum wall thickness Reinforced floor Two
lockable hasps Lifting handles Insulation All necessary wiring shall be
provided for making all system interconnections including: connecting
the solar panels to the charge controller unit, connecting charge
controller output to the battery bank, all interconnections for the
battery bank, connecting the battery bank to the DC/AC invert, and
providing AC outlets for load connection to the system.All solar
modules wiring shall be waterproof interconnects made of 1/2'' outdoor
rated, non-metallic flexible conduit with nylon weathertight fittings.
All battery interconnects wiring shall be 2/0 gauge wire. All inverter
cables shall be welding type of cable with the size being #2/0 gauge.
All remaining cable wire shall be at a minimum 4 gauge. DC Disconnect
The DC Disconnect shall be capable of handling up to 150 amps. The
disconnect shall have room to install shunts. SYSTEM MONITOR: The
system monitor shall be a 3 channel monitor to read battery voltage,
array amperage and load amperage. ENCLOSURES: A combiner enclosure
shall be used for paralleling solar modules. The size of the enclosure
shall be 10'' x 12'' x 6'' with a tolerance of +/- 6''. The enclosures
shall come with lighting protection. An enclosure(s) shall be provided
to house controllers, shunts and fuses. These enclosures shall be the
indoor type of enclosure. 2.9 INSTALLATION MANUAL: A complete
installation manual shall be provided for each system and shall
include, but not be limited to the following: Solar modules setu and
Configuration Battery setup and configuration Electrical connections
Parts list. 2.10 OPERATIONS AND MAINTENANCE MANUAL: Two complete
operations and maintenance manuals shall be provided for the system.
This shall address but not be limited to the following topics:
Autonomous power system initial start up. All regular necessary
maintenance, maintenance schedules and maintenance tools and
facilities. Schematics Fault detection and trouble shooting methods
2.11 WARRANTY: A full warranty shall be provided for a period of 1 year
minimum from installation.2.12 SPARE PARTS The following spare parts
shall be provided over and above the hardware required to instrument
each of the two full systems. Only 1 set of spares is to be provided.
All spares shall meet the performance requirements of sections 2.2. to
2.11.- 2 solar panels- 1 DC/AC inverter- 1 charge controller-
batteries equal to 1/4 of the full battery bank number spare
Interconnect wiring sets for all connections- 2 spare lightning
protection units. TERMS AND CONDITIONS: The terms include FIRM FIXED
PRICE provisions and delivery is anticipated within 90 days after
purchase order award. Delivery shall be FOB destination Newport, Rhode
Island. Award will be made to the responsible offerer proposing the
lowest price meeting the above stated requirements. The applicable
Standard Industrial Classification Code (SIC) is 3433. This acquisition
is 100% SET-ASIDE FOR SMALL BUSINESS. The deadline for submitting
written quotations is on or before 2:00 PM Local Time on 01 DECEMBER
1995 Oral quotes will not be accepted. All quotations must be legibly
written and include DESCRIPTIVE LITERATURE. Send to: Naval Undersea
Warefare Center Division, Newport, Bldg. 11, 1176 Howell Street,
Newport, RI 02841- 1708 (ATTN: Mary Jo Nemec Code 5913K) No RFQ other
than this synopsis will be issued. Certifications will be required of
the successful offerer. Unsuccessful offerors will be notified within
30 days of evaluation. The anticipated award date is 10 December 1995.
(0311) Loren Data Corp. http://www.ld.com (SYN# 0173 19951108\34-0001.SOL)