Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 4,1995 PSA#1482

Federal Aviation Administration, Southern Region, P.O. Box 20636, Atlanta, GA 30320, Attn: ASO-55B

59 -- TRANSFER SWITCHES SOL DTFA06-96-B-50012 DUE 010296 POC Gail Bohannon, Procurement Technician, (404) 305-5785 Installation of Automatic Close Transition Transfer Switch, 400A, 120/208V, 3 phase, 3 pole. This switch will operate in a make-before-break mode without interrupting the load, providing both normal and emergency sources are acceptable. When utility source fails, the switch initiated starting of the engine generator set and transfer the load to the emergency source in an open transition mode. When the utility source is restored for and acceptable time, the switch transfers back to the normal source without interrupting the loan (closed transition). An inphase monitor ensures that closed transition will occur only when the two sources are within +5 electrical degrees. Closed transition period shall not exceed 100 milliseconds. This switch shall be an ASCO 436340047XC in order to allow for compatibility with E/G Set.--Estimated price range $25,000.-$100,000. --Place of performance: FAA locations, Raleigh Durham, NC, Louisville, KY, Tallahassee, FL and Nashville, TN. All responsible bidders will be considered. You may now fax your request for bid documents at (404) 305-5774. (0334)

Loren Data Corp. http://www.ld.com (SYN# 0173 19951201\59-0004.SOL)


59 - Electrical and Electronic Equipment Components Index Page