COMMERCE BUSINESS DAILY ISSUE OF MAY 12,1999 PSA#2344NASA/Glenn Research Center, 21000 Brookpark Road, Cleveland, OH 44135 43 -- WATER PUMP SOL RFQ-124996 DUE 052199 POC Kathleen A. Webb,
Purchasing Agent, Phone (216) 433-6665, Fax (216) 433-2480, Email
Kathleen.A.Webb@grc.nasa.gov WEB: Click here for the latest information
about this notice, http://nais.nasa.gov/EPS/GRC/date.html#RFQ-124996.
E-MAIL: Kathleen A. Webb, Kathleen.A.Webb@grc.nasa.gov. NASA/GRC plans
to issue a Request for Quotation (RFQ) for PR#124996 Sheet 1 of 1
SPECIFICATIONS FOR A HIGH PRESSURE WATER PUMP Item 1. Liquid Pump-
Delaval-CIG Model No. 85250-RDW-007- . A. General Description The
contractor shall provide a liquid pump assembly with the following
salient characteristics: 1. The pump shall be vertically mounted, and
completely assembled and aligned on a mounting base with a coupling
guard. 2. The pump shall be suitable for pumping cooling tower water at
a temperature range of 40 to 90 degrees Fahrenheit. 3. The pump flow
rate shall be a minimum of 96 GPM at 1500 psig. 4. The pump inlet
pressure will be 50 psig. 5. The fluid viscosity shall be 1
centistokes. 6. The inlet and outlet connections for each pump shall be
suitable for mating with Code 61 SAE (Society of Automotive Engineers)
O-ring flanges. The inlet connection shall be 3 inches and the outlet
connection shall be 2 inches. 7. Shall be a positive displacement gear
type pump. 8. The materials used for the pump shall be suitable for use
with water with rust inhibitor. 9. The operating speed for each pump
shall not exceed 1800 rpm. 10. The operating noise level for each pump
shall not exceed 85 dba at a distance of 3 feet from the pump. 11. The
pumps' assembly shall fit in an envelope 84 inches height maximum by 30
inches square. B. Motor Drive The pump shall have an electrical motor
drive with the following characteristics: 1. The pump motor shall be an
open drip-proof continuous duty squirrel cage motor. 2. The motor shall
be suitable for use with 480 volts, 60 hz., 60 phase a.c. power. 3. The
motor shall be rated at 125 horsepower or greater. Item 2.
Documentation The contractor shall supply a total of 3 sets of
documentation. This shall be comprised of 3 sets of pump data curves
and 3 sets of installation, operating, and maintenance instructions. A
recommended list of spare parts shall also be furnished. This
procurement is being conducted under the Simplified Acquisition
Procedures (SAP). NASA/GRC intends to purchase the items from IMO PUMP;
WE ARE INCREASING THE CAPACITY OF THE HIGH PRESSURE COOLING WATER
SYSTEM IN ASCR BY ADDING AN ADDITIONAL PUMP. THE PUMP SPECIFIED IS AN
EXACT DUPLICATE OF THE EXISTING PUMPS IN THE FACILITY. THE FACILITY
PIPING WAS INSTALLED WITH PROVISIONS TO ADD AN ADDITIONAL PUMP. GETTING
AN IMO PUMP THAT IS AN EXACT DUPLICATE WILL RESULT IN MAINTAINING THE
STANDARDIZING OF ALL PUMPS, MINIMIZING THE INSTALLATION COSTS, AND
OPTIMIZING THE MAINTAINANCE SINCE ALL PUMP PARTS WILL BE
INTERCHANGEABLE AND SPARE PARTS WILL BE MINIMIZED. The Government
intends to acquire a commercial item using FAR Part 12. Interested
firms have FIFTEEN (15)days from the publication of this synopsis to
submit in writing to the identified point of contact, their
qualifications/capabilities. Such qualifications/capabilities will be
used solely for the purpose of determining whether or not to conduct
this procurement on a competitive basis. Responses received after the
FIFTEEN (15)days or without the required information will be considered
nonresponsive to the synopsis and will not be considered. A
determination by the Government to not compete this proposed effort on
a full and open competitive basis, based upon responses to this notice
is solely within the discretion of the Government. Oral communications
are not acceptable in response to this notice. All responsible sources
may submit an offer which shall be considered by the agency. An
Ombudsman has been appointed. See Internet Note "B". Posted 05/10/99
(D-SN329461). (0130) Loren Data Corp. http://www.ld.com (SYN# 0235 19990512\43-0006.SOL)
43 - Pumps and Compressors Index Page
|
|